10 / 40 page ![]() 50-621 Kotron Sentinel Models 822, 832 and 842 RF Point Level Switches 7 1.6 Installing a Remote Unit NOTE: Units with remote electronics are provided with the Main Amplifier and a preamplifier. Probe connections are made to the preamplifier. Refer to Section 1.5, Probe Installation for details in installing the probe. 1.6.1 Main Amplifier Remote amplifier assemblies are normally shipped from the factory assembled into an “L” mounting bracket. Install bracket in a location that will isolate the unit from temperatures below -40° F (-40° C) and over +160° F (+70° C) or vibration/mechanical damage. Unit can be mounted up to 2500 feet (760 m) from probe assembly. Intrinsically safe models can be mounted up to 800 feet (240 m) from probe assembly. Location should also offer easy access for wiring, calibration, and maintenance. 1.6.2 Preamplifier 1. Screw the preamplifier housing onto the probe until hand tight. Housing can be wrench tightened to align conduit connection with conduit. 2. Attach white wire from the probe to the connection on the preamplifier – see Figure 11. 3. If using a guarded probe, attach the red wire from the probe to the connection on preamplifier – see Figure 12. 1.6.3 Remote Wiring Connections To connect preamplifier-to-amplifier, use shielded, twisted pair, 22-gauge stranded connectors (part number 09-7146-001). 1. Strip approximately 0.4 inch (10 mm) of outer jacket insu- lation from each end of the shielded, twisted-pair. 2. At the probe preamplifier end, cut the bare shield wire of the cable close to the insulating jacket. 3. Connect the red lead to the positive (+) terminal on the amplifier. Refer to Figure 11 or 12. 4. Connect the black lead to the negative (–) terminal on the preamplifier board. 5. Connect the red lead to positive (+) terminal on the amplifier. 6. Connect black lead to the negative (–) terminal on the amplifier. 7. Connect the shield to the ground ( ) terminal on the amplifier. – (Black) ENT 3871 Top View Preamplifier Side View Preamplifier U4 U5 U2 Q3 Q4 Q1 G P + (Red) Shield Guard (red) Probe (white) + (Red) Shield cut back and taped Guard (red) Probe (white) Side View Main Amplifier – (Black) Figure 12 Remote Electronics with Guarded Probe – (Black) ENT 3871 Top View Preamplifier Side V Preamp – (Black) + (Red) Shield Probe (white + (Red) Shield cut back and taped Side View Main Amplifier Probe (white) U4 U5 U2 Q3 Q4 Q1 G P Figure 11 Remote Electronics with Standard Rigid or Flexible Probe |
|
Link URL |
| Cho đến nay ALLDATASHEET có giúp ích cho doanh nghiệp của bạn hay không? [ DONATE ] |
Alldatasheet là | Quảng cáo | Liên lạc với chúng tôi | Chính sách bảo mật | Liên kết đến bảng dữ liệu | Trao đổi link | Tìm kiếm theo nhà sản xuất All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |