61 / 118 page ![]() 51 T1000 Series UPS 5.6-6kVA Installation and Operation Manual – 91074-005 Display Re- corded Meaning Action BDEPL N Battery Depleted – Battery not within specifications. Call Toshiba for service. BLFE Y Battery Lifetime End – Batteries at end of life. Have batteries replaced immediately. BLFN Y Battery Lifetime Near End – Bat- teries are nearing the end of their expected lifetime. Call Toshiba for service. BOH Y Battery Overheat – Battery not within specifications. Call Toshiba for service. BRPL Y Replace Battery – Battery at end of life expectancy. Replace battery immediately. BSDV N Battery Shutdown Voltage – Bat- tery is discharged down to mini- mum level. UPS will shut down. Secure critical loads until power can be restored. BTSTFL N Battery Test Failed – Battery not within specifications. Call Toshiba for service. BYPOV N Bypass Overvoltage – Bypass voltage exceeds UPS specifica- tions. (See NOTE, Page A-1 “Bypass Voltage”) UPS in Bypass Mode: UPS turns off bypass power to the load until bypass power returns to normal. Check bypass power. BYPUV N Bypass Undervoltage – Bypass voltage less than UPS specifica- tions. (See NOTE, Page A-1 “Bypass Voltage”) UPS in Bypass Mode: UPS turns off bypass power to the load until bypass power returns to normal. Check bypass power. CALL Y Service Call Required – Inspection of the unit is advised. Have inspection/service performed. CHRGOV Y Charger Overvoltage – Battery Charger not within specifications. Call Toshiba for service. CLMT N Current Limit – UPS not within specifications. Call Toshiba for service. DCER Y Display Cable Error – Display cable is disconnected. Connect the display cable. DCANERR N Communication Error between Display and Main Controllers. Call Toshiba for service. EXTBC1 N 1. BC1 Battery String 1, 2, or 3 Disconnected 2. BC1 Over Temperature 3. BC1 Lost Communications with UPS • Recover without power cycle - Must Manually Reset. • Reduce Load on BC, call factory Toshiba for Service • Call Toshiba for Service EXTBC2 N 1. BC2 Battery String 1, 2, or 3 Disconnected 2. BC2 Over Temperature 3. BC2 Lost Communications with UPS • Recover without power cycle - Must Manually Reset. • Reduce Load on BC, call Toshiba for Service • Call Toshiba for Service |
|
Link URL |
| Cho đến nay ALLDATASHEET có giúp ích cho doanh nghiệp của bạn hay không? [ DONATE ] |
Alldatasheet là | Quảng cáo | Liên lạc với chúng tôi | Chính sách bảo mật | Liên kết đến bảng dữ liệu | Trao đổi link | Tìm kiếm theo nhà sản xuất All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |