52 / 118 page ![]() 42 T1000 Series UPS 5.6-6kVA Installation and Operation Manual – 91074-005 Remote Stop The Remote Stop is triggered by an external NO (Normally Open) dry contact switch. Power to the Remote Stop switch is about 10Vdc, and less than 20mA. When the Remote Stop switch is closed, the UPS transfers from Normal/Backup to Bypass after a 1 – 2 sec. detection delay. (See the diagram below) When the closed Remote Stop switch is opened, the UPS transfers from Bypass back to it’s initial state (Normal/Backup) after a 1 – 2 sec. detection delay. If the UPS is in bypass when the Remote Stop is closed, no action is taken. Detection Delay 1-2 Sec. Detection Delay 1-2 Sec. Remote Status Switch Normal / Backup Mode Closed Open Bypass Mode UPS Mode FIGURE 14-2: REMOTE STATUS SHUTDOWN TIMING |
|
Link URL |
| Cho đến nay ALLDATASHEET có giúp ích cho doanh nghiệp của bạn hay không? [ DONATE ] |
Alldatasheet là | Quảng cáo | Liên lạc với chúng tôi | Chính sách bảo mật | Liên kết đến bảng dữ liệu | Trao đổi link | Tìm kiếm theo nhà sản xuất All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|