| công cụ tìm kiếm bảng dữ liệu linh kiện điện tử |
|
TD-70521 bảng dữ liệu(PDF) 3 Page - Macromatic Industrial Controls, Inc. |
|
|
|||||||||||||||||||||||||||||
TD-70521 bảng dữ liệu(HTML) 3 Page - Macromatic Industrial Controls, Inc. |
|
3 / 3 page ![]() 800.238.7474 | www.macromatic.com | sales@macromatic.com 39 Application Data Dimensions Output Contacts: DPDT 10A @ 240V AC/30V DC, 1/2HP @ 120/240V AC (N.O.), 1/3HP @ 120/240V AC (N.C.) B300 & R300; AC15 & DC13 Life: Mechanical: 10,000,000 operations Full Load: 100,000 operations Compatibility: Using a solid state switch to initiate the time sequence is acceptable. See www.macromatic.com/leakage or contact Macromatic for information regarding leakage current limits and other solid state design considerations. Initiating Units with Control Switch Triggers: Timing sequence must be initiated only after input voltage is applied to unit. Minimum required trigger switch closure time is 0.1 seconds. LED: Red LED. Refer to instruction sheet provided with product to determine code for relay & timing status. Approvals: Voltage Tolerance: AC Operation: +10/-15% of nominal at 50/60 Hz. DC Operation: +10/-15% of nominal. Load (Burden): 3 VA Setting Accuracy: Constant Voltage & Temperature w/i specifications: +0.1% of set time or +50ms, whichever is greater For Variable Voltage & Temperature w/i specifications: +1% of set time or +50ms, whichever is greater Repeat Accuracy: Constant Voltage & Temperature w/i specifications: +0.1% of set time or +0.02 seconds, whichever is greater For Variable Voltage & Temperature w/i specifications: +1% of set time or +0.02 seconds, whichever is greater Reset Time: On Delay/Interval/Flasher: 0.1 Seconds Functions with Control Switches: 0.04 Seconds Start-up Time: (Time from when power is applied until unit is timing) 0.05 Seconds for all units Maintain Function Time: (Time unit continues to operate after power is removed) 0.01 Seconds for all units Temperature: Operating: -28o to 65oC (-18o to 149oF) Storage: -40o to 85oC (-40o to 185oF) Insulation Voltage: 2,000 volts All Dimensions in Inches (Millimeters) 2.4 (60) 2.9 (74) 3.0 (77) 1.7 (43) File #E109466 File #LR45565 Low Voltage & EMC Directives EN60947-1, EN60947-5-1 with appropriate socket File #E109466 TD-7 SERIES TIME RANGERTM |
|
|
Link URL |
| Cho đến nay ALLDATASHEET có giúp ích cho doanh nghiệp của bạn hay không? [ DONATE ] |
Alldatasheet là | Quảng cáo | Liên lạc với chúng tôi | Chính sách bảo mật | Liên kết đến bảng dữ liệu | Trao đổi link | Tìm kiếm theo nhà sản xuất All Rights Reserved©Alldatasheet.com |
| Russian : Alldatasheetru.com | Korean : Alldatasheet.co.kr | Spanish : Alldatasheet.es | French : Alldatasheet.fr | Italian : Alldatasheetit.com Portuguese : Alldatasheetpt.com | Polish : Alldatasheet.pl | Vietnamese : Alldatasheet.vn Indian : Alldatasheet.in | Mexican : Alldatasheet.com.mx | British : Alldatasheet.co.uk | New Zealand : Alldatasheet.co.nz |
|
Family Site : ic2ic.com |
icmetro.com |