MODEL: KS2V3
KS2V3 SPECIFICATIONS
ES-3603 Rev.5 Page 2/4
https://www.m-system.co.jp/
GENERAL SPECIFICATIONS
Construction: Panel flush mounting, plug-in
Connection: M3.5 screw terminals
Screw terminal: Chromated steel
Housing material: Flame-resistant resin (gray)
Isolation: Input to SET1 to SET2 to power
Time constant for the input filter (P-dF): 0.0 to 900.0 sec. (0
– 63 %)
Alarm relay switching delay time (P-d1, P-d2): 1 to 999 sec.;
programmable independently for each setpoint
Programming: Front key
Setpoint adjustment (ST1, ST2): -5 to +105 %;
programmable independently for each setpoint
Deadband (hysteresis) (HYS1, HYS2): 0 – 102 %;
programmable independently for each setpoint
Power ON delay (P-d0): 0 to 20 sec.
Read rate: 0.5 sec.
Alarm mode (P-A1, P-A2): Programmable independently for
each setpoint; See Table below.
Param.
Code
(P-A1)
(P-A2)
Alarm Modes
Trip
Operation
Set Value
Latching
Hold*
Relay & LED
Behavior in
Tripped Conditions
0
No alarm
----
----
----
1
High
Absolute value
Without
LED ON
Coil energized
2
Low
Absolute value
Without
LED ON
Coil energized
3
High
Absolute value
With
LED ON
Coil energized
4
Low
Absolute value
With
LED ON
Coil energized
5
High
Absolute value
Without
LED ON
Coil de-energized
6
Low
Absolute value
Without
LED ON
Coil de-energized
7
High
Absolute value
With
LED ON
Coil de-energized
8
Low
Absolute value
With
LED ON
Coil de-energized
*Without latching hold function, the unit is tripped upon starting operation when
the unit is set to Low alarm.
With the function, the unit is NOT tripped until the temperature goes once above
and then below the setpoint.
DISPLAY
Display: 4 digits of 10 mm (.39”) height, 7-segment LED
Scaling range: -1999 to 9999 counts
Measured Value (PV)/Alarm (SET1) display: Red LEDs
Alarm (SET2) parameter display: Green LEDs
PV display at abnormal input: Over range or under range
displayed
Front LEDs
Power indicator: Green LED turns on while the power is
turned on.
Measured Value (PV) indicator: Green LED turns on when PV
display is set.
Alarm SET1 indicator: Red LED turns on when the Alarm
SET1 is in tripped conditions.
Alarm SET2 Indicator: Red LED turns on when the Alarm
SET2 is in tripped conditions.
Engineering unit indication: Sticker label attached;
DC, AC, W, °C, °F, V, mV, A, mA, %, kW, mW,
kV, kA, kvar, Mvar, var, m, mm, kg, kg/h,
kPa, MPa, N·m, Nm3/h, m3/h, m3/sec, m/sec,
ℓ/min, %RH, ℓ, ℓ/h, t/h, rpm, ppm, pH, Pa.
INPUT SPECIFICATIONS
■ DC Voltage: -5 – +105 %
Input resistance: ≥ 1 MΩ
OUTPUT SPECIFICATIONS
■ Relay Contact: SPDT relays
220 V AC @3 A (cos ø = 1)
30 V DC @3 A (resistive load)
Caution: N.O. and N.C. contacts could be conductive at the
same time. DO NOT connect both contacts at the same
time.
Maximum switching voltage: 220 V AC or 30 V DC
Maximum switching power: 660 VA or 90 W
Minimum load: 10 V DC @1 mA
Mechanical life: 2 × 107 cycles with no loads
For maximum relay life with inductive loads, external
protection is recommended.
INSTALLATION
Power consumption
•AC:
Approx. 3.1 VA at 100 V
Approx. 4.1 VA at 200 V
Approx. 4.8 VA at 264 V
•DC: Approx. 1.7 W
Operating temperature: -10 to +55°C (14 to 131°F)
Operating humidity: 30 to 90 %RH (non-condensing)
Mounting: Panel flush mounting with attached
mounting bracket, surface or DIN rail
Weight: 200 g (0.44 lb)
PERFORMANCE
Display accuracy: ±0.5% FS ±1 digit
Setpoint accuracy: Display accuracy ± 0.1 % FS
Trip point repeatability: Included in the setpoint accuracy
Line voltage effect: Included in the display accuracy
Insulation resistance: ≥ 100 MΩ with 500 V DC
Dielectric strength: 1500 V AC @1 minute
(input to SET1 or SET2 to power)
500 V AC @1 minute (SET1 to SET2)



Html Pages

1 2 3 4


bảng dữ liệu tải về

Go To PDF Page


Link URL



Cho đến nay ALLDATASHEET có giúp ích cho doanh nghiệp của bạn hay không?  [ DONATE ] 

Alldatasheet là   |   Quảng cáo   |   Liên lạc với chúng tôi   |   Chính sách bảo mật   |   Liên kết đến bảng dữ liệu    |   Trao đổi link   |   Tìm kiếm theo nhà sản xuất
All Rights Reserved©Alldatasheet.com


Mirror Sites
English : Alldatasheet.com  |   English : Alldatasheet.net  |   Chinese : Alldatasheetcn.com  |   German : Alldatasheetde.com  |   Japanese : Alldatasheet.jp
Russian : Alldatasheetru.com  |   Korean : Alldatasheet.co.kr  |   Spanish : Alldatasheet.es  |   French : Alldatasheet.fr  |   Italian : Alldatasheetit.com
Portuguese : Alldatasheetpt.com  |   Polish : Alldatasheet.pl  |   Vietnamese : Alldatasheet.vn
Indian : Alldatasheet.in  |   Mexican : Alldatasheet.com.mx  |   British : Alldatasheet.co.uk  |   New Zealand : Alldatasheet.co.nz
Family Site : ic2ic.com  |   icmetro.com