M5VS-FD-R/F
AI

The **M5VS-FD-R/F** is a high-performance, ultra-slim signal conditioner (isolator) manufactured by **M-System**. It is designed to accept a DC input signal and provide a standardized DC output, ensuring electrical isolation between the input, output, and power supply.
---
## 1. Technical Specifications
Below is a breakdown of the primary electronic characteristics of the M5VS-FD-R/F.
| Feature | Specification |
| :--- | :--- |
| **Model Function** | DC Signal Conditioner (Isolator) |
| **Input Signal** | 4 – 20 mA DC |
| **Output Signal** | 4 – 20 mA DC |
| **Power Input (R)** | 24V DC |
| **Accuracy** | ±0.1% |
| **Response Time** | ≤ 25 ms (0 – 90%) |
| **Isolation** | 3-way (Input to Output to Power) |
| **Isolation Resistance** | 100 MΩ minimum at 500V DC |
| **Dielectric Strength** | 2000V AC @ 1 minute |
---
## 2. Model Number Breakdown
Understanding the suffix codes is crucial for identifying the specific electronic interface:
### `M5VS-FD-R/F`
* **M5VS**: Series name (Ultra-slim Signal Conditioner).
* **F**: Input Type (4–20 mA DC).
* **D**: Output Type (4–20 mA DC).
* **R**: Power Input (24V DC).
* **F**: Surface Mounting (Bracket included).
---
## 3. Key Electronic Components & Functions
The device operates using three primary internal stages to ensure signal integrity:
### A. Input Stage
* **Shunt Resistor:** Converts the 4–20 mA current into a proportional voltage.
* **Surge Protector:** Protects internal circuits from voltage spikes on the input line.
### B. Isolation Barrier
* **Optical or Transformer Coupling:** The "R/F" designates high-grade isolation. It uses an internal transformer or optocoupler to transmit the signal across a physical gap, preventing ground loops and protecting sensitive PLC/DCS inputs from high-voltage transients.
### C. Output Stage
* **Operational Amplifier:** Reconstructs the signal to ensure the output remains linear to the input.
* **Zero/Span Adjustments:** Located on the front panel, these allow for fine-tuning the calibration of the electronic output.
---
## 4. Connection Diagram (General)
The electronics are wired according to the following pinout logic:
```markdown
Terminal | Function
---------|----------
1 | Input (+)
2 | Input (-)
3 | Output (+)
4 | Output (-)
5 | Power (+) 24V DC
6 | Power (-) 0V
```
---
- ⤷
What is the maximum load resistance supported by the output of the M5VS-FD-R/F?
- ⤷ How do you calibrate the Zero and Span settings on this specific model?
- ⤷ Does this model support HART communication signals through the isolator?