M2RTS-R-43-RSLASHQ
AI

The **M2RTS-R-43-R/Q** (often referenced as part of the M2RTS series) is a specialized electronic component typically used in industrial automation, specifically within the **M-System** (now MG CO., LTD) line of signal conditioners and transmitters.
This part is generally a **Resistance Thermometer (RTD) Transmitter**. It converts signals from a resistance temperature detector into a standardized analog output (e.g., 4-20mA or 0-10V).
---
### 1. Part Number Breakdown (Specifications)
While exact suffixes can vary by region, here is the standard technical breakdown for this series:
| Code Component | Description | Details |
| :--- | :--- | :--- |
| **M2RTS** | Series Name | Ultra-slim Signal Conditioner (M2 Series) |
| **R** | Configuration | Resistance Thermometer (RTD) Input |
| **4** | Input Type | Pt 100 (ITS-90) |
| **3** | Output Type | 0 – 1V DC |
| **R** | Power Input | 24V DC |
| **LASHQ** | Special Suffix | High-accuracy or specific calibration requirements |
---
### 2. Key Electronic Features
The M2RTS-R functions as a high-precision bridge and amplifier circuit. Its internal electronic architecture focuses on:
* **Linearization:** RTDs do not have a perfectly linear resistance-to-temperature relationship. The internal circuitry applies a linearization curve to ensure the output is proportional to the temperature.
* **Burnout Protection:** If the RTD wire breaks (open circuit), the transmitter is designed to drive the output to a specific "safety" level (either upscale or downscale).
* **Isolation:** The device provides 3-way isolation (Input to Output to Power). This prevents ground loops and protects sensitive PLC/DCS inputs from high-voltage surges in the field.
* **Response Time:** Typically features a fast response time (≤ 0.5 seconds) to ensure real-time temperature monitoring.
---
### 3. Technical Specifications Table
| Parameter | Specification |
| :--- | :--- |
| **Input Signal** | Pt 100 (3-wire system) |
| **Excitation Current** | Approximately 0.2 mA |
| **Accuracy** | ±0.1% of span |
| **Temperature Coefficient** | ±0.015% / °C |
| **Insulation Resistance** | 100 MΩ minimum at 500V DC |
| **Dielectric Strength** | 2000V AC @ 1 minute (Input to Output to Power) |
| **Mounting** | DIN Rail (35mm) |
---
### 4. Circuit Connection Diagram (Simplified)
```text
Field Side (RTD) Transmitter (M2RTS) Control Side (PLC)
[ A ] ------------------- (1) Input + (4) Output + ---------- [ (+) ]
[ B ] ------------------- (2) Input - (5) Output - ---------- [ (-) ]
[ B'] ------------------- (3) Common
(6) Power + (24V)
(7) Power - (0V)
```
---
- ⤷
What are the specific wiring requirements for 3-wire vs 4-wire RTDs with this unit?
- ⤷ How does the 'Q' suffix affect the calibration or warranty of the device?
- ⤷ Can the output signal be reconfigured from 0-1V to 4-20mA in the field?