AI

The **FRS-R-16/10** is a specialized industrial fuse manufactured by Eaton (Bussmann Series). It is a part of the Fusetron™ family, known for its dual-element, time-delay capabilities.
### 1. Technical Specifications
Below are the core technical parameters for the FRS-R-16/10 fuse:
| Feature | Specification |
| :--- | :--- |
| **Product Series** | Fusetron™ FRS-R |
| **Amperage Rating** | 1.6 Amps (16/10 A) |
| **Voltage Rating (AC)** | 600 Vac |
| **Voltage Rating (DC)** | 300 Vdc |
| **Interrupting Rating** | 200,000A RMS Symmetrical (AC) / 20,000A (DC) |
| **Fuse Class** | Class RK5 |
| **Body Material** | Fiberglass Tube |
---
### 2. Key Features and Characteristics
#### A. Dual-Element Design
Unlike standard fast-acting fuses, the FRS-R-16/10 contains two distinct elements:
1. **Thermal Element:** Handles low-level overloads. It provides a "time-delay," allowing temporary surge currents (like motor startups) to pass without blowing the fuse.
2. **Magnetic Element:** Provides high-speed response to short circuits or heavy ground faults.
#### B. Current Limitation
As a **Class RK5** fuse, it is highly current-limiting. In the event of a major short circuit, the fuse reacts fast enough to prevent the peak current from reaching its maximum potential, protecting sensitive downstream components from electromagnetic and thermal stress.
#### C. Rejection Feature
The "R" in FRS-R stands for **Rejection**. The fuse has a specific physical groove in the mounting cap. When used with a Class R fuse block, it prevents the installation of non-rejection fuses (like Class H or K) that have lower interrupting ratings, ensuring the safety integrity of the system.
---
### 3. Common Applications
Due to its low amperage (1.6A) and high voltage rating, it is typically used in the following scenarios:
* **Motor Protection:** Small industrial motors where high inrush current occurs at startup.
* **Transformer Protection:** Primary or secondary side protection for control power transformers.
* **Solenoids and Relays:** Protecting inductive loads that experience momentary spikes.
* **General Industrial Circuits:** Used in 480V or 600V power distribution panels.
---
### 4. Comparison: FRS-R vs. FRN-R
It is important not to confuse the FRS-R with the FRN-R series:
* **FRS-R:** Rated for **600 Vac**.
* **FRN-R:** Rated for **250 Vac**.
* *Note: An FRS-R can replace an FRN-R (higher voltage rating), but an FRN-R cannot replace an FRS-R.*
- ⤷
What is the difference between Class RK1 and Class RK5 fuses?
- ⤷ How do you calculate the correct fuse size for a motor branch circuit?