AI

The **PULS CP20.241-R3** is a high-end, DIN-rail mountable industrial power supply designed for critical infrastructure. It belongs to the DIMENSION CP-series and features an integrated **decoupling MOSFET** for N+1 redundancy applications.
---
### 1. Key Technical Specifications
The following table summarizes the primary electrical characteristics of the CP20.241-R3:
| Feature | Specification |
| :--- | :--- |
| **Input Voltage (AC)** | AC 100-240V (-15%/+10%) |
| **Input Voltage (DC)** | DC 110-150V (±20%) |
| **Output Voltage** | DC 24V (Adjustable 24-28V) |
| **Output Current** | 20A (at 24V), 17.1A (at 28V) |
| **Output Power** | 480W |
| **Efficiency** | 95.2% |
| **MTBF** | > 500,000 hours (at 40°C) |
| **Dimensions** | 48 x 124 x 127mm (W x H x D) |
---
### 2. Specialized Electronic Features
#### A. Integrated Redundancy (Built-in MOSFET)
Unlike standard power supplies that require an external diode or redundancy module (like a YR40.241), the **-R3** variant includes an internal decoupling MOSFET.
- **Benefit:** This reduces power losses by up to 85% compared to traditional diode solutions.
- **Function:** It prevents a short circuit on the output of one power supply from affecting the shared DC bus in a redundant system.
#### B. Power Reserves (BonusPower)
The electronics are designed to handle transient loads without voltage drops:
- **Extra Power:** Provides 600W (25A at 24V) for up to 5 seconds.
- **Short-circuit Current:** Can deliver a high peak current to trip downstream circuit breakers effectively.
#### C. Power Factor Correction (PFC)
The unit employs an active PFC circuit that ensures:
- A power factor close to **0.99**.
- Low input harmonic distortion, meeting **EN 61000-3-2** standards.
#### D. DC-OK Relay Contact
A floating relay contact is integrated into the circuitry to monitor the output voltage.
- **Logic:** The contact is closed when the output voltage is > 90% of the adjusted value.
- **Usage:** Essential for PLC status monitoring in automated environments.
---
### 3. Protection Mechanisms
The internal electronic control system protects the unit against several fault conditions:
1. **Over-temperature Protection:** Automatic shut-down with self-recovery.
2. **Over-voltage Protection (OVP):** Limits output to < 32V in case of internal failure.
3. **Transient Protection:** Includes a Varistor (MOV) and gas discharge tube for input surges.
4. **Load Protection:** Electronically limited current to prevent wire overheating during a fault.
---
### 4. Terminal Configuration
| Terminal | Function | Description |
| :--- | :--- | :--- |
| **L, N, PE** | Input | AC Line, Neutral, and Protective Earth |
| **+, -** | Output | Dual terminals for easy wiring of 24V DC |
| **13, 14** | DC-OK | Relays contacts for remote signaling |
- ⤷
What is the difference between the CP20.241-R3 and the standard CP20.241 model?
- ⤷ How do I wire two CP20.241-R3 units for N+1 redundancy?
- ⤷ What are the specific environmental ratings (IP and temperature) for this unit?